Chapter 7. PARAMETER SETUP
7-41
(A2,
B2)
(A
1,
B1)
B-axis
A-axis
1
2
3
4
5
6
7
98
10
11
B-axis (output)
Fixed value
(10000, 10000)
A-axis (input)
Fixed value
(-2000, -2000)
(A3,
B3)
(A
2,
B2)
(A
1,
B1)
(A3,
B3)
(A
2,
B2)
(A
1,
B1)
B-axis B-axis
A-axis A-axis
Excluded
■ Description of table data settings
● t -A . 1 to t -A . b
● t -b . 1 to t -b . b
• These settings are for the A-axis (input) and B-axis (output) settings of input 1 linear-
ization table approximation.
• Both ends of the linearization table are fixed at -2000U, -2000U and 10000U,10000U.
The linearization table is formed by connecting 11 points of table data settings be-
tween the two ends.
• Table data is set not by percentages but directly by engineering unit. When the range
type is set to linear, set scaled values.
• Points on the broken-line, An and Bn, must be set so that they increase in the following
way (A1, B1) = (0, 0), (A2, B2) = (100, 100) and so forth. If set points break this relation-
ship, the point in conflict must be excluded to create the linearization table.
• When two equal points such as A1 and A2 are set for the A-axis, B1 shall be taken as the
output value.