Chapter 4. WIRING
4-12
4-10 Connecting Event Output (relay output)
Event outputs EV1 and EV2 are 1a contact, and event output EV3 is 1a1b. Event outputs are connected on the
standard terminal base.
10
8
9
6
7
4
5
EV1 1a
EV2 1a
EV3 1a1b
Load
Power supply
Load
Power supply
Load
Power supply
Standard terminal base
Contact rating, resistive load
1A (30/250Vdc)
Contact rating, resistive load
1A (30/250Vdc)
Contact rating, resistive load
2A (30/250Vdc)
Minimum switching current: 10mA
When switching small currents, connect a bleeder resistor to allow current flow of
the minimum relay switching input (10mA min.).
Handling Precautions